WIRING COLOR CODES

Tuesday, September 6, 2011

Wiring for AC and DC power distribution branch circuits are color coded for identification of individual wires. In some jurisdictions all wire colors are specified in legal documents. In other jurisdictions, only a few conductor colors are so codified. In that case, local custom dictates the “optional” wire colors.
IEC, AC: Most of Europe abides by IEC (International Electrotechnical Commission) wiring color codes for AC branch circuits. These are listed in Table 2.1. The older color codes in the table reflect the previous style which did not account for proper phase rotation. The protective ground wire (listed as green-yellow) is green with yellow stripe.
IEC, DC: DC power installations, for example, solar power and computer data centers, use
color coding which follows the AC standards. The IEC color standard for DC power cables is
listed in Table 2.5, adapted from Table 2, Cook. [1]
US, AC:The US National Electrical Code only mandates white (or grey) for the neutral power conductor and bare copper, green, or green with yellow stripe for the protective ground.
In principle any other colors except these may be used for the power conductors. The colors adopted as local practice are shown in Table 2.3. Black, red, and blue are used for 208 VAC three-phase; brown, orange and yellow are used for 480 VAC. Conductors larger than #6 AWG are only available in black and are color taped at the ends.
Canada: Canadian wiring is governed by the CEC (Canadian Electric Code). See Table 2.4. The protective ground is green or green with yellow stripe. The neutral is white, the hot (live or active) single phase wires are black , and red in the case of a second active. Three-phase lines are red, black, and blue.

IEC, DC: DC power installations, for example, solar power and computer data centers, use color coding which follows the AC standards. The IEC color standard for DC power cables is listed in Table 2.5, adapted from Table 2, Cook. [1]
US DC power: The US National Electrical Code (for both AC and DC) mandates that the grounded neutral conductor of a power system be white or grey. The protective ground must be bare, green or green-yellow striped. Hot (active) wires may be any other colors except these. However, common practice (per local electrical inspectors) is for the first hot (live or active) wire to be black and the second hot to be red. The recommendations in Table 2.6 are by Wiles. [2] He makes no recommendation for ungrounded power system colors. Usage of the ungrounded system is discouraged for safety. However, red (+) and black (-) follows the coloring of the grounded systems in the table.

Read more...

Resistor Color Codes Example

Example #1

 A resistor colored Yellow-Violet-Orange-Gold would be 47 k with a tolerance of +/- 5%

Example #2
 
A resistor colored Green-Red-Gold-Silver would be 5.2 with a tolerance of +/- 10%.

Example #3
A resistor colored White-Violet-Black would be 97 with a tolerance of +/- 20%. When you see only three color bands on a resistor, you know that it is actually a 4-band code with a blank (20%) tolerance band.

Example #4
A resistor colored Orange-Orange-Black-Brown-Violet would be 3.3 k with a tolerance of +/- 0.1%.

Example #5
A resistor colored Brown-Green-Grey-Silver-Red would be 1.58 with a tolerance of +/- 2%.

Example #6

A resistor colored Blue-Brown-Green-Silver-Blue would be 6.15 with a tolerance of +/- 0.25%.

Read more...

Resistor Color Codes

Monday, September 5, 2011

Components and wires are coded are with colors to identify their value and function.

The colors brown, red, green, blue, and violet are used as tolerance codes on 5-band resistors
only. All 5-band resistors use a colored tolerance band. The blank (20%) ”band” is only used
with the ”4-band” code (3 colored bands + a blank ”band”).

Read more...